Welcome to our site! EDAboard.com is an international Electronics Discussion Forum focused on EDA software, circuits, schematics, books, theory, papers, asic, pld, 8051, DSP, Network, RF, Analog Design, PCB, Service Manuals... and a whole lot more! To participate you need to register. Registration is free. Click here to register now.

why should be the load balanced between all of the 3 phases ?

Status
Not open for further replies.

munzir

Full Member level 6
Full Member level 6
Joined
Oct 11, 2011
Messages
365
Helped
22
Reputation
44
Reaction score
21
Trophy points
1,298
Location
Pak
Activity points
3,795
why should be the load balanced between all of the 3 phases ?

does it have any effect on energy consumption ?

would there be more amps passing through the neutral when any phase is unbalance ?

thanks all of you
 

Three-phase has properties that make it very desirable in electric power systems. The phase currents tend to cancel out one another, summing to zero in the case of a linear balanced load. This makes it possible to eliminate or reduce the size of the neutral conductor; all the phase conductors carry the same current and so can be the same size, for a balanced load.
Three-phase electric power - Wikipedia, the free encyclopedia
 
An important property of a three-phase balanced system is that the phasor sum
of the three line or phase voltages is zero, and the phasor sum of the three line or
phase currents is zero. When the three load impedances are not equal to one another,
the phasor sums and the neutral current (In) are not zero, and the load is, therefore, unbalanced.
The imbalance occurs when an open or short circuit appears at the load.
Any circuit that does not have all loads with the same impedance in all three branches is an unbalanced circuit.

Typical causes:

Unbalanced distribution of single phase loads
Phase-to-phase loads
Unbalanced 3-phase loads
Unequal impedance of cable runs or distribution lines

Typical results:

Current unbalance in 3-phase induction motors can be several times the value of the voltage unbalance,
leading to motor overheating and loss of efficiency
A major cause of premature motor failure
A NEMA rated motor will exceed its nameplate capacity when phase voltage
unbalance exceeds 2%
Damage to sensitive power electronic equipment
Overheating reduces insulation life, causing premature failure of the motor
VFDs may be damaged or in some cases trip

Neutral conductor current increases .
 
also, it allows for a constant power. if you find the voltage*current of each phase, you will see a DC term, and a double-frequency term. with 3 phases, the DC term will add, while the double-frequency term will cancel.
 